Pressure testing a boiler

Boiler must be hydraulic pressure tested about 1.25 times the working pressure. Gag the safety valves and shut of the water gauges. Isolate and blank off parts which are not designed to withstand the pressure( attemperators or superheaters which are only designed to withstand differential pressure
between drum and superheater)fit the pump and required calibrated pressure gauges. Fill drum with water near the present metal temperature (never less than 7 degrees). keep the vents open until water comes through the vent. then pressurize slowly and check for leaks. if leaks are present, rectify and retest.

Comments

Popular posts from this blog

Why atomisation test should not be done in slide type fuel valves

Since very small needle lift is obtained in the test equipment result in an unequal pressure distribution in the cut off shaft resulting in a hard contact in a small area along with high frequency oscillations, low lubricity of test oil will increase the chance of seizure. Full lift and high lubricity of heavy oil eliminates this risk  of seizure during normal operation.( Always open and clean slide type valves before testing as cold sticky heavy oil along with small clearances can cause restriction in the movement of the spindle).