Raising steam from a cold in a boiler

Fill water drum with hot dearated water, initial dosing can be given through the upper manhole cover which is then replaced. Keep the air vent open and fill water upto 1/3rd level in gauge glass or until it shows up in the gauge glass. Check fuel oil system and start circulating diesel oil. start FD fan and
purge the furnace properly. make sure that gauge glass coks are open and start firing the boiler with lowest firing rates. up-to 2.5 - 3 bar...we fire for 10 secs and stop for 10 mins... this is done upto 3 bar ... then close the vent... and then fire for 20 secs and stop for 5 mins..After reaching the working pressure drain the line and crack open the steam stop valve.

Comments

Popular posts from this blog

Why atomisation test should not be done in slide type fuel valves

Since very small needle lift is obtained in the test equipment result in an unequal pressure distribution in the cut off shaft resulting in a hard contact in a small area along with high frequency oscillations, low lubricity of test oil will increase the chance of seizure. Full lift and high lubricity of heavy oil eliminates this risk  of seizure during normal operation.( Always open and clean slide type valves before testing as cold sticky heavy oil along with small clearances can cause restriction in the movement of the spindle).