Why the level of water in boiler gauge glass keep on increasing during normal operation ?

Why the level of water in boiler gauge glass keep on increasing during normal operation ?

As we knows the steam above the water level in gauge glass condenses to form water because the gauge glass is exposed to normal ambient temperature out-side the boiler. but you must have a doubt that the water level should be equalized as the same steam pressure is acting on both the water levels (ie, inside the boiler and in gauge glass). so the level must be equal .


Then how we are getting an increased level in gauge glass???
Its because of the difference in density. The water formed from condensed steam is very pure and density the boiler water is comparatively higher since it contains chemicals , suspended particles etc. so the lesser dense water will  show higher level.

Comments

Popular posts from this blog

Why atomisation test should not be done in slide type fuel valves

Since very small needle lift is obtained in the test equipment result in an unequal pressure distribution in the cut off shaft resulting in a hard contact in a small area along with high frequency oscillations, low lubricity of test oil will increase the chance of seizure. Full lift and high lubricity of heavy oil eliminates this risk  of seizure during normal operation.( Always open and clean slide type valves before testing as cold sticky heavy oil along with small clearances can cause restriction in the movement of the spindle).